Table 19 — Configuration Display Menu (cont)
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
ALLM
ALLM Alert Limit Config Used to configure limits of limit alerts
SPL.O XXX.X F C 65.0 65.0 -10.0 TO 245.0 SPT LO Alert Limit/Occ low space temperature alert limit (occupied mode) ALRTLMTS SPLO
SPH.O XXX.X F C 80.0 80.0 -10.0 TO 245.0 SPT HI Alert Limit/Occ High space temperature alert limit (occupied mode) ALRTLMTS SPHO
SPL.U XXX.X F C 45.0 45.0 -10.0 TO 245.0 SPT LO Alert Limit/Unocc
low space temperature alert limit (unoccupied
mode)
ALRTLMTS SPLU
SPH.U XXX.X F C 100.0 100.0 -10.0 TO 245.0 SPT HI Alert Limit/Unocc
High space temperature alert limit (unoccupied
mode)
ALRTLMTS SPHU
SAL.O XXX.X F C 45.0 45.0 -10.0 TO 245.0 SAT LO Alert Limit/Occ
Low Supply air temperature alert limit (occupied
mode)
ALRTLMTS SAL
SAH.O XXX.X F C 180.0 180.0 -10.0 TO 245.0 SAT HI Alert Limit Occ High Supply air temperature limit (occupied mode) ALRTLMTS SAH
SAL.U XXX.X F C 45.0 45.0 -10.0 TO 245.0 SAT LO Alert Limit/Unocc
Low Supply air temperature alert limit (unoccupied
mode)
ALRTLMTS SALU
SAH.U XXX.X F C 180.0 180.0 -10.0 TO 245.0 SAT HI Alert Limit/Unocc
High Supply air temperature limit (unoccupied
mode)
ALRTLMTS SALH
RAL.O XXX.X F C 60.0 60.0 -10.0 TO 245.0 RAT LO Alert Limit/Occ
Low return air temperature alert limit (occupied
mode)
ALRTLMTS RAL
RAH.O XXX.X F C 90.0 90.0 -10.0 TO 245.0 RAT HI Alert Limit/Occ Low return air temperature limit (occupied mode) ALRTLMTS RAH
RAL.U XXX.X F C 35.0 35.0 -10.0 TO 245.0 RAT LO Alert Limit/Unocc
Low return air temperature alert limit (unoccupied
mode)
ALRTLMTS RALU
RAH.U XXX.X F C 120.0 120.0 -10.0 TO 245.0 RAT HI Alert Limit/Unocc Low return air temperature limit (unoccupied mode) ALRTLMTS RAHU
IRH.L XXX % % 0 0 0 TO 100% RH Low Alert Limit return air humidity low alert limit ALRTLMTS RHL
IRH.H XXX % % 100 100 0 TO 100% RH High Alert Limit return air humidity high alert limit ALRTLMTS RHH
DP.L X.XX H2O pa 0 0 0.0 TO 5.0 SP Low Alert Limit Supply air pressure low level alert limit ALRTLMTS SPL
DP.H X.XX H2O pa 2 2 0.0 TO 5.0 SP High Alert Limit Supply air pressure high level alert limit ALRTLMTS SPH
BP.L X.XX H2O pa -0.25 -0.25 -.26 TO.26 BP Low Alert Limit Building pressure low alert limit ALRTLMTS BPLO
BP.H X.XX H2O pa 0.25 0.25 -.26 TO.26 BP High Alert Limit Building pressure high alert limit ALRTLMTS BPHI
IQ.HI XXX ppm ppm 800 800 0 TO 5000 IAQ High Alert Limit Indoor air IAQ high alert limit ALRTLMTS IAQL